FLD-O2W-SP is a fully encapsulated high-performance sensing probe designed for detecting leaks of refined products or crude oil floating on the water surface in extreme environmental conditions. This probe can also be used as a cost-effective zero-false-alarms hydrocarbon fume detector. UV/ozone resistant, it is specially engineered for reliable operation during long-term immersion in water and in icing conditions and is suitable for polar applications. The maximum length of the sensor probe is limited to 48 in / 122 cm. The sensing probe can be wired to the acquisition module through an optional jumper cable with a maximum length of 300ft. / 90m.
Advanced measurement techniques and data treatment algorithms are used by Naftosense monitoring modules to provide quick detection in a wide temperature range. The sensor is reusable and easily detachable for cleaning.
The FLD-O2W-SP probe is designed to be used exclusively with acquisition modules or intrinsically safe field boxes offered by NAFTOSENSE. It provides industry-standard analog outputs, dry contacts, or serial communication protocols for flexible integration with third-party monitoring panels or PLCs.
FLD-O2W-SP is a passive simple element and is safe for installations in hazardous locations when connected to an intrinsically safe field box or wired through an approved Zener barrier to acquisition modules, alarm panels, or other monitoring equipment installed in the safe area. Please contact NAFTOSENSE for additional information.
Features
FLD-O2W-SP Sensing Probe for Oil-On-Water Leak Detection Features
- Detects very quickly leaks of combustible liquids in a very wide temperature range in under 30 seconds!
- 10-Year Factory warranty on Sensors that are cleanable and reusable after contamination
- Dynamic leak alarms of the sensors relative contamination can be seen on display models
- Fully passive sensor suitable for installations in hazardous locations
- Able to detect quickly fumes/vapors diffused in the soil or aboveground
Specifications
FLD-O2W-SP Sensing Probe for Oil-On-Water Leak Detection Specifications
| Operating Life | 30+ years at 104°F (materials tested in natural ageing conditions) |
| Compatibility | Approved NAFTOSENSE field boxes, monitoring modules and controllers |
| Maximum Diameter | 1.06 in (27 mm) |
| Ingress Rating | IP68 suitable for outdoor/direct burial |
| Operating Temperature Range | -40°F to +185°F (-40°C to +85°C) |
| Maximum Length of Cable/Probe | Sensor Probe: 4 ft. (122 cm) Leader Cable (AWG22 mini): 300 ft. (90 m) |
| Hazardous Locations Classification | IS/ I/ 1/ ABCD/ T4 ; I/ 0/ AEx/ ia IIC T4 ; Class I, Zone 0, Ex ia T4 Class I, Div. 1, Groups A,B,C,D; T4 II 1 G Ex ia IIC T4 Ga |
*FLD-O2W-SP probe can be interfaced with various approved acquisition modules for wired or wireless installations in hazardous locations.
FLD-O2W-SP Sensing Probe for Oil-On-Water Leak Detection Times
| Gasoline, Jet Fuel, Diesel | 20-28 seconds* |
| Light Crude Oil | 45-60 seconds |
| Heavy Crude Oil, Dilbit | 3-4 minutes |
| Motor Oil, Silicone Oil | 8-10 minutes |
| Propane, Butane | 25-30 seconds** |
*These performance metrics are tested and validated by FM Approvals
**When detecting vapors/LPG, the sensing probe must be placed in the lowest point where the fluid will accumulate.
FLD-O2W-SP Sensing Probe for Oil-On-Water Leak Detection Product Codes
| FLD-O2W-SP-6 | Passive Hydrocarbon Sensor Probe of 6-in (15 cm) with 10-ft (3 m) indoor-rated lead cable |
| FLD-O2W-SP-10 | Passive Hydrocarbon Sensor Probe of 10-in (25 cm) with 10-ft (3 m) outdoor-rated lead cable |
| FLD-O2W-SP-24 | Passive Hydrocarbon Sensor Probe of 24-in (61 cm) with 10-ft (3 m) outdoor-rated lead cable |
| FLD-O2W-SP-36 | Passive Hydrocarbon Sensor Probe of 36-in (91 cm) with 10-ft (3 m) outdoor-rated lead cable |
| FLD-O2W-SP-48 | Passive Hydrocarbon Sensor Probe of 48-in (122 cm) with 10-ft (3 m) outdoor-rated lead |
On request, the leader cable can be extended to up to 100 ft (30 m) at the factory. Please consult for pricing options.
Applications
FLD-O2W-SP Sensing Probe for Oil-On-Water Leak Detection Applications
- Leak detection around generators, Subbase tanks, day tanks, and supply and return plumbing in Data Centers, Industrial Facilities, Hospitals, and Commercial buildings
- Fuel / Oil on water Leak detection in outdoor containment areas and sumps
- Detection of leaking fuel oil from boiler installations, Fuel oil storage, and supply and return plumbing
- Leak detection in fuel retail facilities
Q & A
FLD-O2W-SP Sensing Probe for Oil-On-Water Leak Detection Q & A
The probe is rated for hazardous areas when installed with approved equipment.
U.S.: Class I, Division 1, Groups A, B, C, D
ATEX/IECEx: Ex ia IIC T4, Zone 0, II 1 G
It has FM Approvals certifications, meeting standards for intrinsic safety and hydrocarbon leak detection.
Downloads
Download Naftosense FLD-O2W-SP Sensing Probe for Oil-On-Water Leak Detection Datasheet
Talk to one of our technical specialists today at (855) 737-4718, or fill out our online form to learn more.